PRINCIPIA ENGINEER · 1 OF 4

The problem: two documents that live worlds apart.

A review of 1,633 accident reports put a management-of-change failure behind roughly one in eleven; the folklore figure of 80 % has no primary source. Flixborough is the textbook case: a temporary bypass, no change review, 28 dead. The mechanism is always the same shape.

Year 0 · PHAThe Process Hazard Analysis: the systematic study an operations team undertakes to find every credible hazard, for every part of the plant, and the safeguards that stand against it. Every row is true of the plant as built.
Year 1Normal operation.
Year 2 · MOCManagement of Change: the form that asks whether a change is safe, a well tied in, a setpoint moved, a valve relocated. It re-opens the PHA that directly covers the change. Nothing mandates re-opening any other, so the rows elsewhere that rested on the old basis stay as they were.
Year 3The plant runs on a study that is no longer true.
Year 4Still running on it. Somewhere a safeguard is credited with stopping a scenario it no longer can. Nobody knows which.
Year 5 · RevalidationThe next mandated look. If the gap is caught, it is caught here. If a demand came first, it was caught by the plant.
PRINCIPIA ENGINEER · 2 OF 4

The plant, and the engineer

Project Tundra, Oliver County, North Dakota: CO₂ meter stations on the public record, with the downstream documents filled in and labelled.

Our engineer, Cathy. MOC-001 is on her desk. This is what she sees.

HazardDeskPHA softwareDrawVaultdrawing & document controlChangeFlowMOC workflowSafetyReqSIS lifecycleAlarmBasealarm managementTrendStorehistorianProcLibprocedures
+ 1,840 more across 7 systems
OPENED SO FAR

What she does with it today:

Search the driveDozens of PHAs, by unit and by year. By tag, by memory.
Open the sheetsSeven P&IDs to see what the rows mean.
Read the worksheetsEight pages, 35 recommendations, the matrix.
Ask the authorWhich rows rested on the old pressure? If he is still here.
Decide by intuitionWhich safeguards still hold. Nothing on the desk says.
SignThe compressor-unit PHA is updated. Nothing else is.

The last cell is the one the next panel replaces.

The gap is not data. It is reasoning.

Everything Cathy searched for exists and is findable. What does not exist is the capacity to reason across what she didn't simultaneously.

PRINCIPIA ENGINEER · 3 OF 4

The spreadsheet, and the save

Cathy's documents, in the grid she already uses. Nothing new on screen until she saves.

no unsaved changes
ScenarioInitiating eventIEF /yrIPL 1IPL 2Credited timeMitigatedTMELGap
S-1.5.1Loss of upstream overpressure protection at CCS (PSV, PSHH shutdowns)1E-1SIF-101 · 1E-2PAH-1001 operator response · 1E-110 min1E-41E-4metLOPA Rev 1 · row 1
S-1.5.2Pipeline outlet blockage, CCS continues to feed1E-1SIF-101 · 1E-2PAH-1001 operator response · 1E-1101E-41E-4metLOPA Rev 1 · row 2
S-1.2.2PCV-1001 regulator failure, analyzer building1E-2PSV-1001 set 80 psig · 1E-2——1E-41E-4metLOPA Rev 1 · row 5
S-1.7.1Cooler failure, high-temperature CO₂ to pipeline1E-2TSHH-0612/0613 shutdown at 120 °F · 1E-2——1E-41E-4metLOPA Rev 1 · row 6
SIFFunctionSensor · votingTripSIL targetProof-test intervalResponse
SIF-101High inlet pressure → close MOV-1001PS-1001 · 1oo11,750SIL 12 years10 sSRS-101 Rev A
SIF-104Low inlet pressure, well pad 1 → close MOV-1004PS-1004 · 1oo11,200 psigSIL 12 years10 sSRS-104 Rev A
TagSensorSetpoint, psigPriorityClassConsequenceTime to respond
PAH-1001PIT-10011,700Highsafety-relatedHAZOP 1.5.2 · overpressure of ANSI 900 piping; SIF-101 trip at 1,75010 minMADB Rev 3 · row 1
PAL-1004PIT-10051,250MediumoperabilityHAZOP 2.6.1 · phase change of the CO₂, injection upset10 minMADB Rev 3 · row 2
TagAlarmLimit (DCS)Limit (MADB)PriorityLast changed
PIT-1001PAH-10011,7501,700High2025-03-14 · no MOC referenceDCS export 2026-09-30
PIT-1005PAL-10041,2501,250Medium2022-02-18

Before this saves

Nothing commits until every failed or open item is acknowledged, pinned, or the edit is cancelled.
PRINCIPIA ENGINEER · 4 OF 4

What exists, and what can be done

ToolRetrieve the studyLink a row to what it rests onRe-derive on changeSay what it does not know
PHA software (HazardDesk and the like)yeswithin one studynono
MOC workflow (ChangeFlow)attaches itnonono
SIS lifecycle (SafetyReq)yesSRS ↔ SIF ↔ testnono
Asset performance platformsyesHAZOP → LOPA → SIF as recordssnapshots; tracks revalidation datesno
Document control, enterprise searchyesnonono
Principia Engineerreads theirsacross studies, units and documentsevery claim that rested on the change, at saveopen questions, with the row and the owner
We do not replace any of these. We read what they hold and keep the arrows they throw away.

Realpublic record

  • Seven P&ID sheets MM0011–MM0017 (Burns & McDonnell, Rev A, 2021)
  • HAZOP worksheets, three nodes, eight pages (Hoglin Engineering, Feb 2021)
  • All 35 recommendations and the 5×5 risk matrix
  • Design pressure 1,800 psig, ANSI 900 piping, 12,980 ton/day
Source: Project Tundra NEPA record, DOE/NETL, Appendices D–E.

Filled insynthetic, labelled

  • LOPA rows for the scenarios the matrix rates at 6 or above
  • SRS and cause-and-effect for the two shutdown functions
  • Master alarm database and the DCS copy, one tag drifted on purpose
  • Historian excursions, a one-page site procedure, and MOC-001
Limits. Sources read: MM0011–MM0017, HAZOP pp. 1–8, recommendations, matrix, filled-in set v3. Rules applied: 20. Not read: anything outside the meter stations. Nothing here is a safety determination; every output is a question to an engineer with the rows attached.